IP67 protection level, suitable for harsh industrial environments

EC7A-0016B
IP67 I/O module, integrated design, EtherCAT fieldbus, 16 DO, PNP, Using metal material, Power interface using M12-L coding, Covering various types of signals, Rich indicator light function design
What defines this model
Review the published differences attached to this exact model code rather than only the general family.
Based on high-performance EtherCAT ASIC communication chips, direct control, faster speed
Using standard cable wiring is simple and the layout is quick
The configuration is simple, supporting mainstream EtherCAT masters
Place in the system architecture
Treat network, product and field layers as one validation flow.
Network and host-controller compatibility
Channel, interface and function selection
Power, connection, environment and mechanical layout
Technical parameters
Values come from Solidot's current official model record and must be reconfirmed for the product revision.
Interface Parameters
| Bus Connection | 2×M12,4Pin,D-code |
|---|---|
| Protocol | EtherCAT |
| Data Transfer Medium | CAT 5 or above UTP or STP (STP is recommended) |
| Data Transfer Rates | 100Mb/s |
| Distance Between Stations | ≤ 100m(station to station) |
| Electrical Isolation | 500V |
Technical Parameters
| Power interface | 2×M12,4Pin,D-code |
|---|---|
| UStotal current | Max:16A |
| USpower consumption | ≤35mA |
| ULtotal current | Max:16A |
| ULpower consumption | 25mA + Sensor Supply Current + Load Output Current |
| Electrical isolation between GNDS and GNDL | YES |
| Operating Temperature | -25 ~ +70℃ |
| Power Supply | 24 VDC(18V~30V) |
| Relative Humidity | 95 %, no condensation |
| Storage Temperature | -40 ~ +85℃ |
| Protect. Class | IP67 |
| Module Size | 225.5×62.5×32.6mm |
| Weight | 660g |
Digital Output
| Output Interface | 8×M12,5Pin,A-code |
|---|---|
| Output total current | Max:8 A(from UL) |
| Nominal Voltage | 24 VDC(±25%) |
| Number of Outputs | 16 |
| Transistor Polarity | PNP |
| Load Type | ohmic, inductive load |
| Max. Output Current | Max:500 mA(from UL) |
| Port Protection | overcurrent |
| Electrical Isolation | 500V |
| Indicator | Green LED |
| Isolation Method | Optocoupler isolation |
Product images
Images are official source records for the same model.

Official files
Only links published by the manufacturer for this model are listed.
Frequently asked questions
Core checks before selection and commissioning.
Which industrial network does EC7A-0016B support?
Published network support: EtherCAT. Confirm controller compatibility and the complete order code before commissioning.
What are the principal published specifications?
Protocol: EtherCAT; Power interface: 2×M12,4Pin,D-code; Output Interface: 8×M12,5Pin,A-code; Output total current: Max:8 A(from UL)
How should this model be selected?
Evaluate network, channel function, power, environment, wiring and mechanical placement as one configuration. ProControl can verify the final bill of materials.
Other models in this category
Compare protocol, channel architecture and environmental limits.
Technical data and images are based on the current official Solidot product record. Verify revision-sensitive values before ordering or commissioning. Open official record
Validate the right Solidot EC7A-0016B architecture with ProControl
Share the network, signal count, environment and installation constraints; our engineering team will review the complete configuration.