Multiple thermocouple signal types selectable; DC 300V withstand voltage between signal input channels, suitable for grounded probes

XBF-A80TC-8AO
The XBF temperature controller module supports multiple bus protocols including EtherCAT, PROFINET, Modbus TCP, and EtherNet/IP. It offers flexible output configuration, multiple PID control algorithms, and auto-tuning function. Multiple thermocouple signal types are selectable, with features including measurement display, control output, retransmission output, output time accumulation, and sensor wire break detection.
What defines this model
Review the published differences attached to this exact model code rather than only the general family.
The front panel supports channel switching, parameter setting, and status monitoring, intuitive and easy to operate
Features measurement display, control output, retransmission output, output time accumulation, sensor wire break detection, and more
Multiple PID control algorithms available, with auto-tuning function
Place in the system architecture
Treat network, product and field layers as one validation flow.
Network and host-controller compatibility
Channel, interface and function selection
Power, connection, environment and mechanical layout
Technical parameters
Values come from Solidot's current official model record and must be reconfirmed for the product revision.
Technical Parameters
| Power Supply Voltage | DC 24V |
|---|---|
| Power consumption | 2W in no-output state; max. total power consumption 40W with 24V transistor output; max. total power consumption 6W with 4~20mA output |
| Operating Temperature | 0~50℃ |
| Relative Humidity | <85%RH |
| Storage Temperature | -10℃~60℃ |
| Module Size | 47×123×110.5mm |
| Weight | 400g |
| Housing Material | Housing and panel base frame: PA66 (flame retardancy UL94 V-0) |
| Front Film Material | PC film and PEM silicone rubber keypad |
Functional Parameters
| Master Output Type | Transistor open collector output or 4~20mA selectable |
|---|---|
| Transistor Output Capacity | @25℃ DC 24V max. 100mA; derated to 50mA at high temperature; withstand voltage 100V |
| Current/Voltage Output Load Capacity | 4~20mA load < 500Ω; linearity 0.2% |
| Display Update | 2 times per second per channel (sampling rate greater than 80 times per second) |
| Insulation Resistance | Input, output, power supply to housing > 20MΩ |
| Electrostatic Discharge (ESD) | IEC/EN61000-4-2 Contact±4KV/Air±8KV perf.Criteria B |
| EFT/Burst Immunity | IEC/EN61000-4-4 ±2KV perf.Criteria B |
| Surge Immunity | IEC/EN61000-4-5 ±0.5KV perf.Criteria B |
| Voltage Dips and Short Interruptions Immunity | IEC/EN61000-4-29 0%~70% perf.Criteria B |
| Power Failure Data Retention | 10 years, EEPROM write cycles greater than 10 billion |
| Isolation Voltage | Signal input to power supply: 500V AC, 1 min |
Product images
Images are official source records for the same model.

Official files
Only links published by the manufacturer for this model are listed.
Frequently asked questions
Core checks before selection and commissioning.
Which industrial network does XBF-A80TC-8AO support?
Published network support: EtherCAT, PROFINET, EtherNet/IP, Modbus TCP. Confirm controller compatibility and the complete order code before commissioning.
What are the principal published specifications?
Master Output Type: Transistor open collector output or 4~20mA selectable; Transistor Output Capacity: @25℃ DC 24V max. 100mA; derated to 50mA at high temperature; withstand voltage 100V; Current/Voltage Output Load Capacity: 4~20mA load < 500Ω; linearity 0.2%; Power Supply Voltage: DC 24V
How should this model be selected?
Evaluate network, channel function, power, environment, wiring and mechanical placement as one configuration. ProControl can verify the final bill of materials.
Other models in this category
Compare protocol, channel architecture and environmental limits.
Technical data and images are based on the current official Solidot product record. Verify revision-sensitive values before ordering or commissioning. Open official record
Validate the right Solidot XBF-A80TC-8AO architecture with ProControl
Share the network, signal count, environment and installation constraints; our engineering team will review the complete configuration.