Siemens SIRIUS 3RW55 and Veikong VKS8000: soft-starter selection guide

Compare 3RW55 and VKS8000 by motor FLA, starting duty, bypass, torque/adaptive control, motor protection, communications and event logging.

Short answer

What does this page recommend?

A technical alternative, not a drop-in substitute

VKS8000 is an advanced start/stop candidate for pumps, fans, compressors or conveyors, but a 3RW55 selection cannot be converted by motor kW alone. Motor FLA, load torque/inertia, starting time and starts per hour are recalculated.

Veikong

ProControl products to evaluate first

The exact configuration is selected after engineering review.

VKS8000
Veikong

VKS8000

Candidate with built-in bypass and advanced start/stop options; selection is based on motor FLA and starting duty, not motor kW alone.

Open technical page
VKS6000
Veikong

VKS6000

More basic soft-starter family; current, duty cycle, bypass architecture and protection scope are verified before design.

Open technical page
Technical comparison

Similar requirement, different architecture

The table explains product architectures; it is not an exact order-code selection.

Validation areaSiemens SIRIUS 3RW55Veikong / ProControl candidate
Selection basis3RW55 selection uses motor rated current, load class, starting current/time and repetition count.The VKS8000 model table is selected against the same FLA and starting duty; VKS6000 is assessed separately only for more basic functional needs.
Bypass topology3RW55 internal bypass architecture, thermal duty and connection method depend on exact-device documentation.VKS8000 is published with built-in bypass; contactor current, bypass transition, fault behaviour and heat loss are tested.
Start/stop modeSiemens 3RW55 offers torque control and advanced methods for difficult starts.VKS8000 voltage, current-limit, torque and adaptive-start options are tuned on the load; identical names do not mean identical algorithms.
Motor protection3RW55 uses a motor thermal model and sensor-based protection according to configuration.VKS8000 is assessed for over/undercurrent, stall, phase and temperature protection; exact PTC/PT100 input wiring is verified.
Communications and HMI3RW55 can integrate into Siemens automation using PROFINET and other communication modules.VKS8000 connects through Modbus and published communications options; PROFINET requires evidence for the official card/device file.
Logging and maintenance3RW55 diagnostics, events and parameter management are handled with Siemens tools.VKS8000 LCD, event log and parameter upload/download are tested in the maintenance scenario; historical data format is not transferred.
Suitable scenario

When is it worth evaluating?

  • Pumps, fans and compressors with long starts
  • Current-limit and controlled-stop retrofits on conveyors or crushers
  • New panels requiring Modbus monitoring and built-in bypass
Migration gate

Before making a decision

  1. Record motor FLA, service factor, connection and insulation class.
  2. Calculate load-torque curve, inertia, required starting time and starts per hour.
  3. Document 3RW55 bypass, inside-delta, sensor and communications use.
  4. Verify VKS8000 exact current/voltage code plus thermal and protection settings.
  5. Run cold/hot motor starts, stall, phase-loss and emergency-stop tests under load.
Frequently asked

Clear answers about alternatives and migration

Is this a drop-in replacement?

No. It is not a direct substitute until exact model, electrical, protocol-role, mechanical, software and certification checks pass.

What should I provide for selection?

The exact existing code, diagram or I/O list, PLC/network data, supply, environment and special functions in use.

Is the same motor kW rating enough to select a VKS8000 model?

No. Motor FLA, mains voltage, load torque, starting time/current, starts per hour, ambient conditions and bypass duty must be calculated together.

This content compares manufacturer-published data under the same project requirement; it does not guarantee direct substitution or project compatibility. ProControl engineering must validate exact model, revision, protocol, electrical, safety and environmental conditions.