VKS8000 is a soft starter with a built-in bypass contactor for controlled motor starting and stopping. It should be evaluated separately from a variable-frequency speed drive. Current and starting duty, separate control supply and operator-panel options must be checked together during selection.

VKS-8000 Bypass Soft Starter

Technical specifications

Ratings refer to the linked document revision. Confirm the nameplate, motor current and operating conditions for the exact selection.

Technical specifications

Built-in bypass
A built-in bypass contactor is provided; the brochure says an external bypass contactor is unnecessary for normal use.
PDF p. 5

Electrical ratings

Rated current range
Brochure rated operating-current range: 22–1600 A.
PDF p. 6PDF p. 8
690 V power range
The 690 V specification table lists 11–1200 kW; this voltage is a separate-order option.
PDF p. 4PDF p. 6
Main supply
Supply variants: 220 / 380 / 690 V AC, ±10%.
PDF p. 8
Control supply
Control supply L/N: 110–220 V AC or 230–440 V AC; tolerance +10%/−15%.
PDF p. 8
Mains frequency
Mains frequency: 45–66 Hz.
PDF p. 8

Technical specifications

Overload capacity
Brochure overload values: 150% Ie for 35 s and 200% Ie for 15 s.
PDF p. 6

Motor and process control

Starting functions
Voltage ramp, current-limit start, square-torque start, kick start and jog functions are listed.
PDF p. 7
Acceleration profiles
Adaptive acceleration includes early, constant and late acceleration profiles.
PDF p. 4

Operation

Display languages
Chinese/English LCD; other languages are described as custom requests.
PDF p. 4
Event log
Ten timestamped event records.
PDF p. 5
Parameter transfer
Parameter upload/download and password locking of changes.
PDF p. 4PDF p. 7

Technical specifications

Panel protection
The remote operator panel can reach IP65 with its optional mounting kit; this is not the enclosure rating of the whole starter.
PDF p. 5PDF p. 7
Ground-fault option
Ground-fault protection is explicitly marked optional.
PDF p. 7

Commissioning and operation

Control-circuit simulation
The control circuit can be simulated without three-phase power or a load motor.
PDF p. 7

Communication and options

Communications
Factory protocol is Modbus; PROFIBUS is a custom configuration.
PDF p. 7

Control inputs and outputs

Control input ratings
Control inputs: active 24 V DC / 8 mA.
PDF p. 8
Control contacts
Start and jog are listed as normally open; stop and external fault are normally closed.
PDF p. 8
Temperature input
Motor temperature can be monitored with an external PT100 sensor.
PDF p. 7PDF p. 8
Analogue output
Analogue output is listed as 0–20 mA or 4–20 mA; terminal numbering conflicts with the diagram.
PDF p. 8
Auxiliary supply
Auxiliary 24 V DC output is rated 200 mA.
PDF p. 8

Protection functions

Protection functions
Phase sequence, undercurrent, frequency, motor overload, instantaneous overcurrent, heatsink temperature, starting timeout, current imbalance and SCR short circuit are monitored.
PDF p. 7

Document revision and selection notes

IP65 applies to the optional remote-panel installation, not the whole starter

IP65 applies to the optional remote-panel installation, not the whole starter. A complete verified installation manual and model/current matrix were unavailable; confirm the enclosure nameplate.
PDF p. 5

p4 calls the normal 380 V range 5.5–400 kW; p6 lists 11–800 kW

p4 calls the normal 380 V range 5.5–400 kW; p6 lists 11–800 kW. The first frame drawing says 5.5–55 kW but its table says 11–55 kW.
PDF p. 4PDF p. 6

p8 prose places AO at 11/12 but the diagram at 12/13; bypass relay prose says 22/23/24 while the diagram says 25/26/27

p8 prose places AO at 11/12 but the diagram at 12/13; bypass relay prose says 22/23/24 while the diagram says 25/26/27. Do not publish these terminal numbers as wiring instructions.
PDF p. 8

p8 lists both 10 A resistive and 5 A at 250 V AC without identifying the second load class.

p8 lists both 10 A resistive and 5 A at 250 V AC without identifying the second load class.
PDF p. 8

Important note 5

Conflicting/revision-specific document information; confirm the ordered unit: The 380 V specification table says 11–800 kW; another page gives a different ordering range, so confirm the specific model.
PDF p. 6

Manufacturer drawings

Open connection and dimension drawings in the manufacturer’s original PDF. For installation, use the complete manual matching the exact product model.

Open drawing in PDF
VKS8000 — dimensions; confirm the power-range discrepancy
PDF p. 6

Information needed for selection

Providing the following information helps our technical team select the correct product and accessories.

  • What are the motor nameplate current, supply voltage and load type?
  • What are the starts per hour, starting duration and current-limit target?
  • Do the control supply and bypass arrangement match the ordered model?
  • Are soft stop, a remote panel and a motor-temperature sensor required?

Let us verify your application

For VKS-8000 Bypass Soft Starter selection, share motor, supply, control, environment and duty-cycle data with our engineering team.

Request a technical review