XB6-C01SP
Solidot · Serial Communication Module

XB6-C01SP

Provides a three-in-one interface of RS232/RS485/RS422, supports Modbus RTU/

Modbus RTUSerial Communication Module
Communication ProtocolModbus RTU、Modbus ASCII
Communication interface typeRS232、RS485、RS422
Number of Channels1 channel

What defines this model

Review the published differences attached to this exact model code rather than only the general family.

Published capability

Six communication modes can be set: MRM/MRS/MAM/MAS/FP/PT

Published capability

Supports three types of communication interfaces: RS485/RS422/RS232

Published capability

Supports two types of communication protocols: Modbus RTU/ASCII

Published capability

Compact structure, small footprint

Place in the system architecture

Treat network, product and field layers as one validation flow.

Robot or serial device

Vendor protocol and data map

Solidot gateway

Connectivity, data mapping and diagnostics

PLC network

Field data delivered to the control system

Technical parameters

Values come from Solidot's current official model record and must be reconfirmed for the product revision.

Interface Parameters
Connection MethodPlug in spring connection
Data Transfer MediumX-bus Backplane Bus
Data Transfer Rates6Mb/s
Electrical IsolationYes
Technical Parameters
Number of Channels1 channel
Communication interface typeRS232、RS485、RS422
Communication ProtocolModbus RTU、Modbus ASCII
Baud rate1200bps~115200bps
Power70mA@5VDC
Operating Temperature-10~+60℃
Relative Humidity95% with no condensation
Storage Temperature-20℃~+75℃
Protect. ClassIP20
Module Size106×73×25.7mm
Weight90g
Functional Parameters
Communicate Mode0:MRM(Modbus RTU Master mode)1:MRS(Modbus RTU Slave mode)2:MAM(Modbus ASCII Master mode)3:MAS(Modbus ASCII Slave mode)4:FP(FreePort)5:PT(PassThrough)
Serial Baud0:1200 bps1:2400 bps2:4800 bps3:9600 bps4:19200 bps5:38400 bps6:57600 bps7:115200 bps
Serial Stop0:1 Bit1:2 Bits
Serial Parity0:None1:Odd parity2:Even parity
Serial WordFormat0:8 Bits1:7 Bits
Modbus Slave ID1~247(Valid in slave mode)
Modbus Slave Respond Delay0~65535 ms (Slave response delay / Master station polling delay / FP output data transmission interval, default 50ms)

Product images

Images are official source records for the same model.

Frequently asked questions

Core checks before selection and commissioning.

Which industrial network does XB6-C01SP support?

Published network support: Modbus RTU. Confirm controller compatibility and the complete order code before commissioning.

What are the principal published specifications?

Communication Protocol: Modbus RTU、Modbus ASCII; Communication interface type: RS232、RS485、RS422; Number of Channels: 1 channel; Protect. Class: IP20

How should this model be selected?

Evaluate network, channel function, power, environment, wiring and mechanical placement as one configuration. ProControl can verify the final bill of materials.

Other models in this category

Compare protocol, channel architecture and environmental limits.

Manufacturer source

Technical data and images are based on the current official Solidot product record. Verify revision-sensitive values before ordering or commissioning. Open official record

Validate the right Solidot XB6-C01SP architecture with ProControl

Share the network, signal count, environment and installation constraints; our engineering team will review the complete configuration.

Contact engineering