VFD200A Pump Application Drive
VFD200A is a general-purpose asynchronous-motor drive with V/F and vector-control functions. Closed-loop control requires a PG card; Modbus-RTU is the documented available bus. Select power, current and mounting dimensions against the duty rating and nameplate.

Series representative image — the manufacturer’s VFD200A model image could not be verified.
Technical specifications
Ratings refer to the linked document revision. Confirm the nameplate, motor current and operating conditions for the exact selection.
Supply
| Supply classes | Single-phase 220 V and three-phase 380 V models. PDF p. 6 |
|---|
Output and load capacity
| Frequency range | Vector and V/F control: 0–500 Hz. PDF p. 6 |
|---|---|
| G-duty overload | 150% rated current for 60 seconds; 180% for 3 seconds. PDF p. 6 |
| P-duty overload | 120% rated current for 60 seconds; 150% for 3 seconds. PDF p. 6 |
Motor and process control
| Control modes | Sensorless vector, V/F and closed-loop vector with an additional PG card. PDF p. 6 |
|---|---|
| Starting torque | SVC: 150% at 0.5 Hz; FVC: 180% at 0 Hz. PDF p. 6 |
| Speed-control range | SVC 1:100; FVC 1:1000. PDF p. 6 |
| Speed stability | SVC ±0.5%; FVC ±0.02%. PDF p. 6 |
| Carrier frequency | 0.5–16 kHz, automatically adjusted to load characteristics. PDF p. 6 |
| Process functions | Built-in PID and simple PLC for operation at up to 16 speeds. PDF p. 7 |
| Motor parameter groups | Switching among four motor-parameter sets. PDF p. 7 |
Communication and options
| Standard communication | Modbus-RTU over RS485. PROFIBUS-DP/CANopen are described as future support, not available standard functions. PDF p. 7 |
|---|
Control inputs and outputs
| Analog input types | AI1: 0–10 V; AI2: 0–10 V or 0–20 mA, depending on selection settings. PDF p. 15 |
|---|
Protection functions
| Protection functions | Phase loss, overcurrent, overvoltage, overtemperature, overload, undervoltage and motor short-circuit detection at power-up. PDF p. 8 |
|---|---|
| Motor temperature sensing | PT100/PT1000 motor-temperature sensing requires the optional I/O expansion card. PDF p. 7 |
Operating environment
| Environment | Indoor use; −10…+50 °C with derating above +40 °C; below 95% RH, non-condensing. PDF p. 8 |
|---|---|
| Storage/altitude | Storage −20…+60 °C; the environment table specifies altitude below 1000 m. PDF p. 8 |
Commissioning and operation
Model and dimension tables
Check the units and document revision in each table. Wide tables can be scrolled horizontally on small screens.
Power and output current — as printed
The smallest rating printed as 0.7 kW conflicts with the related 0.75G dimension row and requires nameplate confirmation. The listed powers do not replace G/P duty selection.
| Supply | Printed power (kW) | Output current (A) | Source |
|---|---|---|---|
| 1~220V | 1.5 | 7 | PDF p. 6 |
| 1~220V | 2.2 | 11 | PDF p. 6 |
| 3~380V | 1.5 | 3.7 | PDF p. 6 |
| 3~380V | 2.2 | 5.1 | PDF p. 6 |
| 3~380V | 3.7 | 9 | PDF p. 6 |
| 3~380V | 5.5 | 13 | PDF p. 6 |
| 3~380V | 7.5 | 17 | PDF p. 6 |
| 3~380V | 11 | 25 | PDF p. 6 |
| 3~380V | 15 | 32 | PDF p. 6 |
| 3~380V | 18.5 | 38 | PDF p. 6 |
| 3~380V | 22 | 45 | PDF p. 6 |
| 3~380V | 30 | 60 | PDF p. 6 |
| 3~380V | 37 | 75 | PDF p. 6 |
| 3~380V | 45 | 90 | PDF p. 6 |
| 3~380V | 55 | 110 | PDF p. 6 |
| 3~380V | 75 | 150 | PDF p. 6 |
| 3~380V | 90 | 176 | PDF p. 6 |
| 3~380V | 110 | 210 | PDF p. 6 |
| 3~380V | 132 | 250 | PDF p. 6 |
| 3~380V | 160 | 300 | PDF p. 6 |
| 3~380V | 185 | 340 | PDF p. 6 |
| 3~380V | 200 | 380 | PDF p. 6 |
| 3~380V | 220 | 420 | PDF p. 6 |
| 3~380V | 250 | 470 | PDF p. 6 |
| 3~380V | 280 | 520 | PDF p. 6 |
| 3~380V | 315 | 585 | PDF p. 6 |
| 3~380V | 350 | 650 | PDF p. 6 |
| 3~380V | 400 | 725 | PDF p. 6 |
| 3~380V | 450 | 820 | PDF p. 6 |
| 3~380V | 500 | 900 | PDF p. 6 |
T4 frame dimension groups
Table uses −T4 suffix and G/P duty labels; verify the ordering code and current installation drawing with the manufacturer.
| Printed model group | Mounting A (mm) | Mounting B (mm) | H (mm) | Width W (mm) | Depth D (mm) | Hole (mm) | Source |
|---|---|---|---|---|---|---|---|
| 0.75G/1.5P,1.5G/2.2P,2.2G/3.7P,3.7G/5.5P | 107 | 175 | 185 | 118 | 167 | 4.5 | PDF p. 133 |
| 5.5G/7.5P | 107 | 175 | 185 | 118 | 187 | 4.5 | PDF p. 133 |
| 7.5G/11P,11G/15P | 148 | 235 | 247 | 160 | 190 | 5.5 | PDF p. 133 |
| 15G/18.5P,18.5G/22P,22G/30P | 205 | 305 | 320 | 220 | 205 | 5.5 | PDF p. 133 |
| 30G/37P,37G/45P | 180 | 416 | 432 | 255 | 234.5 | 7 | PDF p. 133 |
| 45G/55P,55G/75P | 244 | 497 | 518 | 300 | 260 | 9 | PDF p. 133 |
| 75G/90P,90G/110P,110G/132P | 300 | 598 | 620 | 390 | 300 | 11 | PDF p. 133 |
| 132G/160P,160G/185P | 350 | 745 | 780 | 480 | 360 | 12 | PDF p. 133 |
| 185G/200P,200G/220P (hanging) | 400 | 830 | 855 | 500 | 360 | 12 | PDF p. 133 |
| 185G/200P,200G/220P (cabinet) | — (not specified) | — (not specified) | 1138.4 | 500 | 360 | — (not specified) | PDF p. 133 |
| 220G/250P,250G/280P,280G/315P,315G/350P (hanging) | 480 | 942 | 970 | 650 | 418 | 13 | PDF p. 133 |
| 220G/250P,250G/280P,280G/315P,315G/350P (cabinet) | — (not specified) | — (not specified) | 1320 | 650 | 418 | — (not specified) | PDF p. 133 |
| 350G/400P,400G/450P,450G/500P,500G (cabinet) | — (not specified) | — (not specified) | 1720.4 | 800 | 490 | — (not specified) | PDF p. 133 |
Document revision and selection notes
The overview states 5 DI/2 AO, while the terminal table shows X1–X6 and one AO
The overview states 5 DI/2 AO, while the terminal table shows X1–X6 and one AO. Exact I/O counts require hardware/manual confirmation.
PDF p. 8PDF p. 15
The first power-table row is printed as 0.7 kW, while the related dimension row says 0.75G
The first power-table row is printed as 0.7 kW, while the related dimension row says 0.75G. Confirm the exact nameplate before ordering.
PDF p. 6PDF p. 133
An enclosure IP rating was not verified in the inspected technical tables.
An enclosure IP rating was not verified in the inspected technical tables.
PDF p. 8
Manufacturer drawings
Open connection and dimension drawings in the manufacturer’s original PDF. For installation, use the complete manual matching the exact product model.
PDF p. 133
Technical documents
Information needed for selection
Providing the following information helps our technical team select the correct product and accessories.
- Select G/P duty, motor current and the PG card when required.
- Confirm required I/O counts and mounting dimensions against the hardware revision to be supplied.
Let us verify your application
For VFD200A Pump Application Drive selection, share motor, supply, control, environment and duty-cycle data with our engineering team.