Skip to Content
Veikong · Solar Pump Inverters

VFD500-PV Solar Pump Inverter

VFD500-PV converts photovoltaic power into AC output for solar pumping. AC backup, water-level control and remote monitoring are configured for the application. VFD500M-PV is a separate family; model codes and current ratings are not interchangeable.

VFD500-PV Solar Pump Inverter

Technical specifications

Ratings refer to the linked document revision. Confirm the nameplate, motor current and operating conditions for the exact selection.

Supply

DC input — 220 V class
July 2024 manual: 200–450 VDC; maximum open-circuit voltage (Voc) 450 V.
PDF p. 6
DC input — 380 V class
350–800 VDC; maximum Voc 800 V.
PDF p. 6
Recommended Vmpp
220 V class: 250–400 V, recommended point 305 V. 380 V class: 450–600 V, recommended point 530 V.
PDF p. 6
Operation versus standby
P23.02 allowing a threshold down to 160 V does not establish 160 V as the normal operating input limit for the 220 V class.
PDF p. 49

Output and load capacity

Motor output
1/3-phase 220 VAC for the 220 V class; 3-phase 380–480 VAC for the 380 V class.
PDF p. 6
Output frequency
50/60 Hz applications; the manual lists a 600 Hz maximum. The motor's permissible speed must be checked separately.
PDF p. 6
Overload
150% of rated output current for 1 minute.
PDF p. 6

Motor and process control

MPPT
The July 2024 user manual specifies MPPT efficiency above 99%.
PDF p. 6
MPPT + PID
The brochure specifies combined MPPT and PID control.
PDF p. 6
Water/light conditions
Sleep at high water level or weak light; wake-up at low water level or sufficient sunlight.
PDF p. 6
Operator panel
LED keypad is standard; LCD keypad is optional.
PDF p. 5

Communication and options

Remote monitoring
GPRS monitoring is optional; the module has separate connection and operating documentation.
PDF p. 6

Commissioning and operation

AC/DC changeover
The AC/DC switching-board solution is described in Appendix A; board and external-circuit selection belong to the installation design.
PDF p. 74
Long motor cable
For motor cables longer than 100 m, evaluate an output reactor, dV/dt filter or sine-wave filter.
PDF p. 10
Commissioning checks
Check PV Vmp/Voc, motor power/current, cable length, motor insulation and fault records together.
PDF p. 18

Protection functions

Enclosure protection
The manual states IP20/IP21; confirm the enclosure class for the exact ordered model.
PDF p. 6

Operating environment

Operating temperature
−10…+50 °C; derating is required above +40 °C.
PDF p. 6
Altitude
Above 1000 m, the manual specifies 1% derating per additional 100 m.
PDF p. 6
Cooling
Air-cooled construction.
PDF p. 6

Selection information

PV array and motor selection
The manual recommends PV power around 1.5 times pump power as a design guideline, not a universal guarantee. Total Voc must stay below the maximum.
PDF p. 6

Model and dimension tables

Check the units and document revision in each table. Wide tables can be scrolled horizontally on small screens.

VFD500-PV 380–480 V table

The 11 kW code is printed VFD50040T01100-PV (missing hyphen); do not generate an ordering code automatically. Rated currents apply at 380 V; reassess at 400/415/440 V.

Printed model codeMaximum DC input current (A)Rated output current (A)Pump power (kW)Source
VFD500-40T00150-PV94.21.5PDF p. 7
VFD500-40T00220-PV125.62.2PDF p. 7
VFD500-40T00400-PV16.59.44PDF p. 7
VFD500-40T00550-PV23.9135.5PDF p. 7
VFD500-40T00750-PV30.6177.5PDF p. 7
VFD50040T01100-PV39.22511PDF p. 7
VFD500-40T01500-PV493215PDF p. 7
VFD500-40T01850-PV503718.5PDF p. 7
VFD500-40T02200-PV604522PDF p. 7
VFD500-40T03000-PV816030PDF p. 7
VFD500-40T03700-PV907537PDF p. 7
VFD500-40T04500-PV1309045PDF p. 7
VFD500-40T05500-PV15011055PDF p. 7
VFD500-40T07500-PV20015275PDF p. 7
VFD500-40T09000-PV25017690PDF p. 7
VFD500-40T11000-PV300210110PDF p. 7
VFD500-40T13200-PV360253132PDF p. 7
VFD500-40T16000-PV430304160PDF p. 7
VFD500-40T18500-PV500360185PDF p. 7
VFD500-40T20000-PV550380200PDF p. 7
VFD500-40T22000-PV620426220PDF p. 7
VFD500-40T25000-PV680465250PDF p. 7
VFD500-40T28000-PV760520280PDF p. 7
VFD500-40T31500-PV850585315PDF p. 7
VFD500-40T35500-PV975650355PDF p. 7
VFD500-40T40000-PV1050725400PDF p. 7
VFD500-40T45000-PV1200820450PDF p. 7
VFD500-40T50000-PV1350900500PDF p. 7
VFD500-PV 220 V table

July 0.75/1.5/2.2 kW currents differ from April; this table follows July.

Printed model codeMaximum DC input current (A)Rated output current (A)Pump power (kW)Source
VFD500-20T00075-PV6.74.20.75PDF p. 8
VFD500-20T00150-PV9.97.51.5PDF p. 8
VFD500-20T00220-PV14.19.42.2PDF p. 8
VFD500-20T00400-PV22.6174PDF p. 8
VFD500-20T00550-PV30255.5PDF p. 8
VFD500-20T00750-PV40327.5PDF p. 8
VFD500-20T01100-PV604511PDF p. 8
VFD500-20T01500-PV816015PDF p. 8
VFD500-20T01850-PV907518.5PDF p. 8
VFD500-20T02200-PV1309022PDF p. 8
VFD500-20T03000-PV15011230PDF p. 8
VFD500-20T03700-PV20015237PDF p. 8
Brochure frame dimensions

Do not use mounting dimensions without matching the frame letter to the nameplate and same-brochure model table; revision differences exist.

FrameA (mm)B (mm)H (mm)H1 (mm)Width W (mm)Depth D (mm)Hole (mm)Mounting screwsSource
A87206.5215— (not specified)1001705M4x16PDF p. 6
B113239.5250— (not specified)1301805M4x16PDF p. 6
C153299310— (not specified)1701936M5x16PDF p. 6
D1653503703352101966M5x16PDF p. 6
E218438452.54242602307M6x16PDF p. 6
F25053555552032027510M8x20PDF p. 6
G28062064060535029010M8x20PDF p. 6
H28069571566037031311M8x25PDF p. 6
I28070572567036033811M8x25PDF p. 6
J36079581676249035811M10x25PDF p. 6
K36079581676249035811M10x25PDF p. 6
L45010451075100555045013M12x30PDF p. 6
M6301013149597073045013M12x30PDF p. 6
N66010651575109578545013M12x30PDF p. 6

Document revision and selection notes

April documents say 160–450 VDC; July says 200–450 VDC

April documents say 160–450 VDC; July says 200–450 VDC. July is preferred; do not promise the older lower limit.
PDF p. 6PDF p. 6PDF p. 4

Some small VFD500M current ratings differ between brochure and manual; verify the exact M-family nameplate.

Some small VFD500M current ratings differ between brochure and manual; verify the exact M-family nameplate.
PDF p. 5PDF p. 7

The webpage advertises up to 710 kW; the inspected physical table stops at 500 kW

The webpage advertises up to 710 kW; the inspected physical table stops at 500 kW. No verified 710 kW variant is added.
PDF p. 7

Manufacturer drawings

Open connection and dimension drawings in the manufacturer’s original PDF. For installation, use the complete manual matching the exact product model.

Open drawing in PDF
Frame dimensions and pump application examples
PDF p. 6
Open drawing in PDF
Current-revision model/current selection table
PDF p. 7

Information needed for selection

Providing the following information helps our technical team select the correct product and accessories.

  • Provide motor voltage, phase count, power and nameplate current, PV-array Vmp/Voc and motor-cable length.
  • Match the exact VFD500-PV or VFD500M-PV code and manual revision. Specify required boards separately for AC backup and remote monitoring.

Let us verify your application

For VFD500-PV Solar Pump Inverter selection, share motor, supply, control, environment and duty-cycle data with our engineering team.

Request a technical review