Skip to Content
XB6S-A40TM
Solidot · Temperature Module

XB6S-A40TM

The new generation slice type 4-channel temperature acquisition module, supports types of sensors such as thermal resistors and thermocouples. It uses the X-bus bottom bus, adapts to the XB6S series coupler, the module occupies a small space and has high practicality, providing guarantees for users' high-speed data collection, system configuration optimization, simplification of field wiring, and improvement of system reliability.

Temperature Module
Bus InterfaceReed Contact
Input FilteringSingle-channel filtering, configurable (levels 1-10)
Analog Inputs4

What defines this model

Review the published differences attached to this exact model code rather than only the general family.

Published capability

Measurement types support TC, TD, RTD

Published capability

Sensitivity: 0.1℃, supports single-channel filter settings

Published capability

Temperature sensor supports disconnection detection

Published capability

Supports 50Hz, 60Hz, 10Hz, noise suppression configuration

Place in the system architecture

Treat network, product and field layers as one validation flow.

Coupler

Control network and backplane bus

I/O modules

Digital, analogue, temperature and special-function channels

Terminals and devices

Power, wiring and field-device matching

Technical parameters

Values come from Solidot's current official model record and must be reconfirmed for the product revision.

Interface Parameters
Data Transfer MediumX-bus
Bus InterfaceReed Contact
Data Transfer Rates6Mb/s
Electrical IsolationYES
Technical Parameters
Module Abnormality Self-RecoverySupport
diagnosisSupport
AlarmSupport
Firmware UpgradeSupport
Operating Temperature-20℃~+60℃
Power Supply5VDC(4.5V~5.5V)
Relative Humidity95 %, no condensation
Storage Temperature-40℃~+80℃
Protect. ClassIP20
Module Size106.4*25.7*72.3mm
Weight110g
Analog
Input FilteringSingle-channel filtering, configurable (levels 1-10)
Power consumption0.5W
Sensor TypeTC, RTD, TD
Conversion TimeTC:29ms/ch 115ms/8ch RTD,TD:73ms/ch 290ms/8ch
SensitivityTC,RTD:0.1℃ TD:±0.1Ω
Noise Suppression50Hz、60Hz、10Hz、none
Excitation Current<2mA
Electrical Isolation500VAC
Analog Inputs4
Resolution16bit(int type)
AccurateTC:±0.3% @25℃ (F.S.), ±0.5% @-20~60℃ (F.S.) RTD:±0.1% @25℃ (F.S.),±0.3% @-20~55℃ (F.S.) TD:±0.1% @25℃ (F.S.),±0.3% @-20~55℃ (F.S.)
Input Resistance≥10KΩ
IndicatorGreen LED

Product images

Images are official source records for the same model.

Frequently asked questions

Core checks before selection and commissioning.

Which industrial network does XB6S-A40TM support?

Network support must be confirmed from the exact model code and current official documentation.

What are the principal published specifications?

Bus Interface: Reed Contact; Input Filtering: Single-channel filtering, configurable (levels 1-10); Analog Inputs: 4; Input Resistance: ≥10KΩ

How should this model be selected?

Evaluate network, channel function, power, environment, wiring and mechanical placement as one configuration. ProControl can verify the final bill of materials.

Other models in this category

Compare protocol, channel architecture and environmental limits.

Manufacturer source

Technical data and images are based on the current official Solidot product record. Verify revision-sensitive values before ordering or commissioning. Open official record

Validate the right Solidot XB6S-A40TM architecture with ProControl

Share the network, signal count, environment and installation constraints; our engineering team will review the complete configuration.

Contact engineering